MultiTherm ULT-170 Heat Transfer Fluid
MultiTherm ULT-170 ® heat transfer fluid extends low-end operating ranges far beyond the boundaries of most competitive brands. Even at temperatures below -170°F (-112°C), the fluid remains pumpable.
MultiTherm ULT-170 ® allows for cost-effective retrofits with minimal equipment modifications. Choose its thermal stability, environmental performance, biodegradability and cost effectiveness for many critical applications.
|
Viscosity of MultiTherm ULT - 170®
|
| Recommended temperature range: |
| -170°F (-112°C) to 325°F (163°C) |
| Typical Properties of MultiTherm ULT-170® |
Composition: Hydrocarbon Blend
Appearance and Color: Transparent, clear to light yellow |
|
Property
|
US units
|
SI units
|
|
Freeze Point
|
-200°F
|
-129°C
|
|
Boiling Point:
|
384-354°F
|
176-179°C
|
|
Flash Point
(closed cup):
|
127°F
|
53°C
|
|
Flash Point
(open cup):
|
142°F
|
61°C
|
|
Fire Point:
|
147°F
|
64°C
|
|
Autoignition Temperature:
|
730°F
|
388°C
|
|
Critical Temperature 1 :
|
729°F
|
387°C
|
|
Critical Pressure 1 :
|
33.6 atm
|
34 bar
|
|
Avg. Molecular Weight:
|
135
|
|
Dielectric Constant:
|
2.3
|
1 Estimated
|
Density, Specific Heat, Thermal Conductivity of MultiTherm ULT-170® |
Typical Properties of MultiTherm ULT -170®
US Units |
Temp.
°F |
Density
lb/ft3 |
Specific Heat
Btu/lb °F |
Btu/(hr)(ft2)(°F /ft) |
| -170 |
59.1 |
0.312 |
0.0956 |
| -120 |
57.8 |
0.337 |
0.0916 |
| -60 |
56.2 |
0.367 |
0.0868 |
| -20 |
55.1 |
0.387 |
0.0836 |
| 0 |
54.6 |
0.397 |
0.0820 |
| 20 |
54.0 |
0.407 |
0.0804 |
| 60 |
53.0 |
0.427 |
0.0772 |
| 120 |
51.4 |
0.457 |
0.0724 |
|
Typical Properties of MultiTherm ULT-170®
SI Units |
Temp.
°C |
Density
kg/m3 |
Specific Heat
kJ/kg K |
Thermal Conductivity
W/m K |
| -125 |
956.76 |
1.287 |
0.1627 |
| -100 |
937.5 |
1.375 |
0.1577 |
| -75 |
918.24 |
1.462 |
0.1527 |
| -50 |
898.98 |
1.550 |
0.1477 |
| -25 |
879.72 |
1.637 |
0.1427 |
| 0 |
860.46 |
1.725 |
0.1377 |
| 50 |
821.94 |
1.900 |
0.1277 |
| 100 |
783.42 |
2.075 |
0.1177 |
|